Application
Classification
Nominal sizes
Filter classes
Filter groups
Filter classes
Construction
Useful additions
Construction features
Materials and surfaces
Standards and guidelines
Fractional efficiency ePM10 [%] to ISO 16890 | 60 | – | – |
Fractional efficiency ePM1 [%] to ISO 16890 | – | 65 | 90 |
Initial differential pressure [Pa] at nominal volume flow rate | 60 | 80 | 130 |
Maximum operating temperature [°C] for frames made of plastic | 60 | 60 | 60 |
Maximum operating temperature [°C] for frames made of galvanised sheet steel | 90 | 90 | 90 |
final differential pressure [Pa] | 300 | 300 | 300 |
Changing the filter/Final differential pressure
The aim is to find the optimum of the longest possible service life with energetically low differential pressure and safe hygiene. A fixed, recommended value for the final differential pressure can tempt people to insist on keeping to this value, irrespective of its usefulness and today's standards with regard to, for example, energy saving, sustainability or resource conservation. To save costs and energy, we generally recommend the use of technically high-quality filters with low initial differential pressure and a flat differential pressure curve. In addition, the preferred criterion for a filter change should be the differential pressure. For further information, please refer to the installation and maintenance instructions.
Specification text
Pocket filter PFN made of NanoWave® medium as prefilters or final filters for the separation of fine dust in ventilation and air conditioning systems. Wedge-shaped filter pockets ensure ideal airflow conditions. Highest possible dust holding capacity with an extremely low initial differential pressure due to a multi-layer filter medium with a prefilter layer and a layer of corrugated extra fine fibres. Pocket filters made of NanoWave® medium are available in standard sizes with variable numbers of pockets and pocket depth, filter groups ePM10 and ePM1 according to ISO 16890. Pocket filters made of NanoWave® medium are Eurovent-certified and compliant with VDI 6022 in terms of hygiene. The PFN-EX pocket filters with optional EX protection may be used in areas with a potentially explosive atmosphere of zones 1 and 2, as well as zones 21 and 22 (EX II 2G Ex h IIC Gb and EX II 2D Ex h IIIB Db). It is mandatory to connect the filters to the earth potential. All conductive and dissipative parts must be connected together and grounded. Conductive dusts are excluded from the application. Under no circumstances should metallic foreign materials enter the filter.
Ambient temperature range: -40 °C ≤ Ta ≤ +80 °C
Materials and surfaces
Construction
Sizing data
Life cycle assessment
A life cycle assessment is available for the product series in form of an Environmental Product Declaration (EPD) that has been checked and published by a programme holder.
PFN | – | ePM1 | – | 90 % | – | PLA | – | 25 | / | 592 × 592 × 600 | × | 10 |
| | | | | | | | | | | | | | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 |
Share page
Rekommendera denna sida
Rekommendera denna sida ved att senda en link på mail.
Dela sidan
Tack för din rekommendation!
Din rekommendation har skickats och bör anlända inom kort tid.
Kontakt
Vi är här for dig
Vänligen skriv ditt meddelande och ärende
Kontakt
Tack for ditt meddelande!
Ditt meddelande har skickats och kommer att behandlas inom kort tid. Vår serviceavdelning återkommer til dig så snart vi har möjlighet.
Kontakt
Vi är här for dig
Vänligen skriv ditt meddelande och ärende
Kontakt
Tack for ditt meddelande!
Ditt meddelande har skickats och kommer att behandlas inom kort tid. Vår serviceavdelning återkommer til dig så snart vi har möjlighet.