TFP-TC-S_3d_02psd.png
TFP
TFP-TC-S_3d_03psd.png
TFP

Easy cleaning and validation

TFP_img_11psd.png
Construction with removable spigot

Construction with removable spigot

doc_graphic_000009.png
Tested to VDI 6022

Getest volgens VDI 6022

TFP-TC-S_3d_02psd.png
TFP-TC-S_3d_03psd.png
TFP_img_11psd.png
doc_graphic_000009.png

TFP   

For critical air cleanliness and very critical hygiene requirements, suitable for ceiling installation


 

Pharmaceutical clean room terminal filters as a final filter stage with Mini Pleat filter panels for the separation of suspended particles. Used in highly sensitive areas in pharmaceuticals, medicine, and biology

  • Mini Pleat filter panels with downstream fluid seals meet the highest hygiene requirements
  • Easy, time-saving, and secure filter change
  • Air terminal device is held in place by magnets and can be hinged down to facilitate cleaning and validation; filter change with patented turn clip
  • Newly designed supports for mounting in false ceilings
  • Robust, welded construction
  • Compact construction, suitable for low ceilings
  • Various diffuser face plates to ideally meet individual requirements
  • Horizontal or vertical connection
  • Removable spigot for installation into closed ceilings in case of horizontal connection
  • For air cleanliness classes 5 to 8 according to ISO 14644-1
  • Meets the hygiene requirements of VDI 6022

 

 

 


General information

Application

  • Pharmaceutical clean room terminal filter for ceiling installation as final filter stage and for air distribution in sensitive areas of the pharmaceutical industry
  • Fitting of filter elements for the separation of suspended particles such as aerosols, toxic dusts, viruses, bacteria from the supply or extract air.


Variants

  • TC-S: Top entry circular spigot, top lateral suspension lugs
  • TC-FC: Top entry circular spigot, with supports for mounting in false ceilings
  • SC-S: Side entry circular spigot, top lateral suspension lugs
  • SC-FC: Side entry circular spigot, with supports for mounting in false ceilings
  • SCR-S: Side entry circular spigot, removable, top lateral suspension lug
  • SCR-FC: Side entry circular spigot, removable, with supports for mounting in false ceilings


 Construction



  • Sheet steel, powder-coated, RAL 9010, pure white



Nominal sizes

  • 400, 500, 600, 625 [mm]


Attachments

  • FD: Ceiling swirl diffuser
  • TDF: Ceiling swirl diffuser


Useful additions

  • Mini Pleat filter panels (MFP)
  • Suitable filter elements to be ordered separately



Special features

  • Compact construction
  • Flush ceiling installation
  • Removable spigot for installation into closed ceilings
  • Diffuser face plate can be hinged down
  • Filter change with patented turn clip
  • Supports for mounting in false ceilings



Construction features

  • Welded filter casing with sealing frame for fitting filter elements, with a seal on the downstream side
  • Mounted pressure measurement points to monitor the operating differential pressure and with internal measuring tube



Materials and surfaces

  • Casing and diffuser face plate made of sheet steel, powder-coated RAL 9010, pure white


Commissioning



  • Fitting of filter elements with a fluid seal on the downstream side
  • Pressing of the filter element is performed using four patented turn clips
  • Diffuser face plate is hinged and held in place by magnets; no additional tools required



Standards and guidelines

  • Hygiene meets the requirements of VDI 6022, VDI 3803, DIN 1946 Part 4, ÖNORM H 6021 and ÖNORM H 6020, SWKI VA 104-01 and SWKI 99-3, and EN 16798



Maintenance

  • Diffuser face plate can be hinged down to facilitate disassembly and cleaning
  • Particulate filter need not be removed for cleaning (seal on downstream side)
  • Easy change of filter elements due to special frame profile; no additional fluid sealing frame is necessary


Teknisk information

Function, Specification text, Order code

  • FUNCTION
  • SPECIFICATION TEXT
  • ORDER CODE

Pharmaceutical clean room terminal filter type TFP for ceiling installation as final filter stage and for air distribution in sensitive areas of the pharmaceutical industry. Fitting of filter elements for the separation of suspended particles such as aerosols, toxic dusts, viruses and bacteria from the supply or extract air. Welded filter casing with sealing frame for fixing the Mini Pleat filter panels, with a fluid seal on the downstream side. With side entry or top entry spigot. Side entry spigot can be removed if desired. Pressing the Mini Pleat filter panels is performed by four patented turn clips. Casing with mounted pressure measurement points to monitor the operating differential pressure and with internal measuring tube. Diffuser face plate made of sheet steel, powder-coated (RAL 9010), types FD and TDF; can be hinged down to facilitate disassembly and cleaning. Leakage test for each casing.


 Special features



  • Compact construction
  • Flush ceiling installation
  • Removable spigot on the side for installation in closed ceilings
  • Air terminal device can be hinged down
  • Filter change with patented turn clip
  • Supports for mounting in false ceilings



Materials and surfaces

  • Casing and air terminal device made of sheet steel, powder-coated, RAL 9010, pure white


Constructions



  • Sheet steel, powder-coated, RAL 9010, pure white

 

 

 



TFPSC-SFD/600×198×330
||||||
123456

1 Type
TFP Pharmaceutical clean room terminal filters 


2 Variant
TC-S Top entry circular spigot, top lateral suspension lugs
TC-FC Top entry circular spigot, with supports for mounting in false ceilings
SC-S Side entry circular spigot, top lateral suspension lugs
SC-FC Side entry circular spigot, with supports for mounting in false ceilings
SCR-S Side entry circular spigot, removable, top lateral suspension lugs
SCR-FC Side entry circular spigot, removable, with supports for mounting in false ceilings           

3 Air terminal device
FD
TDF 

4 Nominal size [mm]
400
500
600
625 

5 Spigot diameter [mm]
D 

6 Casing height [mm]
G1

Variants, Dimensions

  • VARIANTS
  • DIMESNIONS

Product examples


Product specific data TFP-TC-S

All weights are net, without packaging

NSB × H × T∅DG₁KHMJLL₂kg
400295 × 295 × 8515825036537130839833534810
500395 × 395 × 8519825046547140849843544815
600495 × 495 × 8519825056557150859853554821
625520 × 520 × 8519825059059653362356057323

① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ ~ Weight

Product specific data TFP-TC-FC

All weights are net, without packaging

NSB × H × T∅DG₁KHMJLL₂FCkg
400295 × 295 × 8515825036537130839831444275 – 17512
500395 × 395 × 8519825046547140849841454275 – 17517
600495 × 495 × 8519825056557150859851464275 – 17523
625520 × 520 × 8519825059059653362353966775 – 17525

① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Suspended ceiling dimensions ⑩ ~ Weight

Product specific data TFP-SC-S

All weights are net, without packaging

NSB × H × T∅DG₁KHMJLL₂Gkg
400295 × 295 × 8515833036537130839833534821511
500395 × 395 × 8519833046547140849843544821516
600495 × 495 × 8519833056557150859853554821522
625520 × 520 × 8519833059059653362356057321524

① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ ~ Weight

Product specific data TFP-SC-FC

All weights are net, without packaging

NSB × H × T∅DG₁KHMJLL₂GFCkg
400295 × 295 × 8515833036537130839831444221575 – 17512
500395 × 395 × 8519833046547140849841454221575 – 17517
600495 × 495 × 8519833056557150859851464221575 – 17523
625520 × 520 × 8519833059059653362353966721575 – 17525

① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑩ ~ Weight

Product specific data TFP-SCR-S

All weights are net, without packaging

NSB × H × T∅DG₁KHMJLL₂Gkg
400295 × 295 × 8515833036537130839833534821511
500395 × 395 × 8519833046547140849843544821516
600495 × 495 × 8519833056557150859853554821522
625520 × 520 × 8519833059059653362356047321524

① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑩ ~ Weight

Product specific data TFP-SCR-FC

All weights are net, without packaging

NSB × H × T∅DG₁KHMJLL₂Gkg
400295 × 295 × 8515833036537130839831444221512
500395 × 395 × 8519833046547140849841454221517
600495 × 495 × 8519833056557150859851464221523
625520 × 520 × 8519833059059653362353966721525

① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑩ ~ Weight

Nedladdningar

produkt information

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://api.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://psp40.onventis.com https://psp22.onventis.com https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Rekommendera denna sida

Rekommendera denna sida ved att senda en link på mail.

Fält markerade med en (*) är obligatoriska.

Dela sidan

Tack för din rekommendation!

Din rekommendation har skickats och bör anlända inom kort tid.


Kontakt

Vi är här for dig

Vänligen skriv ditt meddelande och ärende

Fält markerade med en (*) är obligatoriska.

Kontakt

Tack for ditt meddelande!

Ditt meddelande har skickats och kommer att behandlas inom kort tid. Vår serviceavdelning återkommer til dig så snart vi har möjlighet.

Kontakt

Vi är här for dig

Vänligen skriv ditt meddelande och ärende

Bifoga (max 10MB)

Fält markerade med en (*) är obligatoriska.

Kontakt

Tack for ditt meddelande!

Ditt meddelande har skickats och kommer att behandlas inom kort tid. Vår serviceavdelning återkommer til dig så snart vi har möjlighet.